Image for Illustration purposes only. Actual product may vary
Call for Pricing - 888-671-2883
Typically Ships in: 1 day
Returnable: Yes
Coil operating limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at = 70 C)
Connecting capacity main circuit
Bar 24 mmRigid Al-Cable 25 ... 150 mmRigid Cu-Cable 6 ... 185 mm
Connecting terminals main poles
Flat type c/w screws and bolts
Conventional free-air thermal current
acc. to IEC 60947-4-1, Open Contactors q = 40 C 275 A
Maximum electrical switching frequency
(AC-1) 300 cycles per hour(AC-2 / AC-4) 150 cycles per hour(AC-3) 300 cycles per hour
Maximum mechanical switching frequency
3600 cycles per hour
Mechanical durability
5 million
Number of auxiliary contacts NC
1
Number of auxiliary contacts NO
1
Number of main contacts NC
0
Number of main contacts NO
3
Rated breaking capacity AC-3
8 x Ie AC-3
Rated control circuit voltage
50 Hz 110 ... 115 V60 Hz 115 V
Rated impulse withstand voltage
Main Circuit 8 kV
Rated insulation voltage
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 600 V
Rated making capacity AC-3
10 x Ie AC-3
Rated operational current DC-1
(110 V) 2 Poles in Series, 40 C 275 A(220 V) 3 Poles in Series, 40 C 275 A
Rated operational current DC-3
(110 V) 2 Poles in Series, 40 C 275 A(220 V) 3 Poles in Series, 40 C 275 A
Rated operational current DC-5
(110 V) 2 Poles in Series, 40 C 275 A(220 V) 3 Poles in Series, 40 C 275 A
Rated operational power AC-3
(415 V) 90 kW(440 V) 90 kW(500 V) 110 kW(690 V) 132 kW(380 / 400 V) 90 kW(220 / 230 / 240 V) 55 kW
Rated operational voltage
Main Circuit 690 V
Short-circuit protective devices
gG Type Fuses 355 A
A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V.Operated with control voltage, versions from 24...690 AC, 50 and 60 Hz
| Brand | Superlok |
| Model | SRUI-4-2 |
| Brand | Flexco |
| Model | 04144 |
| Brand | ACME |
| Model | T2A533601S |