# IFM SA4120 Flow sensor - MROSupply.com

***IFM SA4120 Flow sensor***



## Product details:

- Catalog number: SA4120
- SKU: 96944137
- Price: ***$530.31*** Each
- Shipping: ***FREE SHIPPING***  ON ORDERS OVER $100
- Brand: [IFM](https://www.mrosupply.com/brands/ifm/)
- Category: 
    - [Automation](htts://www.mrosupply.com/automation/)
- Unit of measure: each
- Returns: Yes


## Product images:
- https://assets.mrosupply.com/images/noimage.webp


## Product attributes;

  
- Accuracy: ± (10 % MW + 2 % MEW)
  

  
- Accuracy [K]: ± 2 / + 8; (flow velocity > 20 % VMR and 20 °C: ± 2)
  

  
- Ambient Temperature (°C): -40...80
  

  
- Ambient temperature [°C]: -40...80
  

  
- Analog Current Output (Ma): 4...20
  

  
- Analog current output [mA]: 4...20; (scalable)
  

  
- Analog End Point AEP (M/S): 6...30
  

  
- Analog end point AEP [m/s]: 6...30
  

  
- Analog Start Point ASP (M/S): 0...24
  

  
- Analog start point ASP [m/s]: 0...24
  

  
- Communication Interface: IO-Link
  

  
- Connector: 1 x M12; coding: A; Contacts: gold-plated
  

  
- Current Consumption (Ma): < 100
  

  
- Current consumption [mA]: < 100
  

  
- Dimensions (mm): Ø 8 / L = 192
  

  
- Dimensions [mm]: Ø 8 / L = 192
  

  
- Display Range (M/S): 0...36
  

  
- Display range [m/s]: 0...36
  

  
- Display Unit: 6 x LED, green (%, m / s, l / min, m³ / h, °C, 10³)
  

  
- Dynamic Response T05 / T09 (S): 30 (T09)
  

  
- Dynamic response T05 / T09 [s]: 30 (T09); (Flow velocity: ≥ 10 m/s)
  

  
- Electrical Design: PNP / NPN
  

  
- Factory Setting / Mode = (REL): 1237
  

  
- File Number UL: E174189
  

  
- Frequency At The End Point FRP (Hz): 100...1000
  

  
- Frequency at the end point FRP [Hz]: 100...1000
  

  
- Frequency End Point, FEP (M/S): 6.6...30
  

  
- Frequency end point, FEP [m/s]: 6.6...30
  

  
- Frequency of The Output (Hz): 0...1000
  

  
- Frequency of the output [Hz]: 0...1000
  

  
- Greatest Sensitivity (M/S): 0.6...30
  

  
- Greatest sensitivity [m/s]: 0.6...30
  

  
- Housing: Tubular
  

  
- Installation: Recommended for Pipe Diameters
  

  
- IO-Link Revision: 1.1
  

  
- Material: stainless steel (1.4404 / 316L); PBT-GF20; PBT-GF30
  

  
- Materials (Wetted Parts): Stainless Steel (1.4404 / 316L)
  

  
- Max. load [Ω]: 350
  

  
- Max. voltage drop switching output DC [V]: 2.5
  

  
- Maximum Load (Ω): 350
  

  
- Maximum Voltage Drop Switching Output DC (V): 2.5
  

  
- Measured Values: alphanumeric display, red / green 4-digit
  

  
- Measuring Principle: Calorimetric
  

  
- Measuring Range (°C): -20...100
  

  
- Measuring range [°C]: -20...100
  

  
- Media: Air
  

  
- Medium Temperature (°C): -20...100
  

  
- Medium temperature [°C]: -20...100
  

  
- Min. process cycle time [ms]: 3
  

  
- Minimum Process Cycle Time (Ms): 3
  

  
- Mode = (ABS): 1238
  

  
- MTTF (Years): 131
  

  
- MTTF [years]: 131
  

  
- Number of Analog Outputs: 1
  

  
- Number of Digital Outputs: 2
  

  
- Number of inputs and outputs: Number of digital outputs: 2; Number of analog outputs: 1
  

  
- Operating Mode: Relative; Absolutely Gaseous
  

  
- Operating Voltage (V): 18...30 DC
  

  
- Operating voltage [V]: 18...30 DC; (to SELV/PELV)
  

  
- Output Function: Normally Open / Closed
  

  
- Overload Protection: Yes
  

  
- Pack quantity: 1 pcs.
  

  
- Permanent Current Rating of Switching Output DC (Ma): 250
  

  
- Permanent current rating of switching output DC [mA]: 250
  

  
- Power-on Delay Time (S): 10
  

  
- Power-on delay time [s]: 10
  

  
- Probe Length L (mm): 100
  

  
- Probe length L [mm]: 100
  

  
- Process Connection: Clamp fitting Ø 8 mm
  

  
- Process data analog: 2
  

  
- Process data binary: 2
  

  
- Protection: IP 65; IP 67
  

  
- Protection Class: III
  

  
- Repeatability: ± (3 % MW + 0, 6 % MEW)
  

  
- Required master port class: A
  

  
- Reset Point Rp (M/S): 0.6...28.6
  

  
- Reset point rP [m/s]: 0.6...28.6
  

  
- Resolution (M/S): 0.2
  

  
- Resolution [m/s]: 0.2
  

  
- Resolution [°C]: 0.2
  

  
- Response Time (S): 7
  

  
- Response time [s]: 7
  

  
- Reverse Polarity Protection: Yes
  

  
- SDCI Standard: IEC 61131-9
  

  
- Set Point SP (M/S): 2...30
  

  
- Set point SP [m/s]: 2...30
  

  
- Setting Range (M/S): 0.6...60
  

  
- Setting range [m/s]: 0.6...30
  

  
- Short-circuit Protection: Yes
  

  
- SIO mode: Yes
  

  
- Special feature: Gold-plated contacts
  

  
- Storage Temperature (°C): -40...100
  

  
- Storage temperature [°C]: -40...100
  

  
- Switching Status: 2 x LED, yellow
  

  
- Temperature Drift: ± 0, 005 K / °C
  

  
- Total Number of Outputs: 2
  

  
- Transmission type: COM2 (38, 4 kBaud)
  

  
- Type of Short-circuit Protection: Yes (Non-latching)
  