Item: 1
Service: Functional Replacement
Mounting: Horizontal Foot with F1 Main T-Box
Quantity: 1
HP Rating: 800
Speed: 900 RPM
Phase-Hz-Volts: 3-60-4000 VAC
Enclosure: WP-I
Estimated Frame Size: 400-1250
Service Factor: 1.15
Bearing Construction: Anti-Friction
Rotor Construction: Copper Bar
Insulation Class: Class F - Epoxy Resin
Ambient Temperature: 40 deg. C
Temperature Rise: B @ 1.0 SF by RM
Altitude: 3300 Ft. ASL
Coupling Method: Direct
Load Inertia (LB-FT^2): < NEMA
Rotation: Bi-Directional CCW viewed from NDE
Starting Method: VFD
Starting Duty: 2 Cold / 1 Hot starts
Hazardous Area: NON Hazardous
Applicable Standards: NEMA MG 1 / IEEE 112 / CSA
Certifying Body: CSA
Motor Only Offering:
Functional Replacement of SN: 02291497M
Main Terminal Oversized Box : NEMA TYPE I Cast Terminal Box - 4.0" NPT
> Main Terminal Box - NEC Ground Lug
> Rated IP55
•Insulation System Capable of Withstanding an Immersion Test in Accordance with NEMA MG-1 31
•Stator: Class F VPI insulation
•Stator: Heavy Duty Bracing
•Assembly: NEMA F-1 Assembly
•Space Heater, 120 V Single Phase
•Stator RTD's - Feature: (6) 10 Ohm Copper DIN Standard, 2/phase, 3-wire
•Bearing RTD's - Feature: (2) 10 Ohm Copper Std, single-element, 3-wire, 1/brg
•Aux. Terminal Box(es) (F1 Location): Separate boxes, 1 space heater .75" NPT and 1 temp instrumentation leads 1.25" NPT
•Dowel Pin Provisions
•Vertical Jacking Provisions
•Severe Duty, Corrosion-Resistant, Rust-lnhibitive Paint System on Frame (RAL 6012).
• Standard Non-Witnessed Routine Testing per IEEE-112 Method:
A Standard Routine Test includes the following:
No-Load Current
No-Load Watts Input
No-Load Speed
Winding Resistance
High-Potential Test (Dielectric Test)
Locked-Rotor Current
Locked-Rotor Watts Input
Visual Inspection
Vibration Check - Overall Vibration Displacement Measurements Tested Per NEMA MG1-12