HPS DM660KD DIT 660 KVA 480-240 AL Drive Isolation Transformers
MODEL DM660KD
Contact supplier for technical support on: 4153324100
$31,080.00 Each
Account holders see our lower price and live availability.
Prices are subject to change
FREE SHIPPING ON ORDERS OVER $100
Select Quantity
Returnable: Yes
Approval
CSA, UL
Availability
Custom sizes, ratings and styles available upon request
Certification
CSA certified
Drive isolation transformer
3ph 660kVA 480V-240Y/139V 60Hz AL
Duty
General duty
Efficiency regulation
Not specified (USA)
Enclosure dimensions
66in/1677mm(H), 51.5in/1309mm(W), 43.4in/1103mm(D)
Enclosure finish
ANSI 61 grey, UL50
Enclosure IR window
No
Enclosure PN (NPL)
NJ3-N3R
Enclosure type
Type 3R / IP24
Frequency
60 Hz
Impedance (std)
5.5% - 7.5%
Insulation class
220°C
Insulation System
220°C (150°C rise)
Material
Copper and aluminum available
Motor HP
Not Selected
Nameplate
HPS standard
Net weight (NPL)
2900 lb / 1320 kg
Number of secondaries
1 (6-pulse)
Phase
Three phase
Primary connection
Delta
Primary FCAN (std)
2x2.5%
Primary FCBN (std)
2x2.5%
Primary termination (std)
Mounting pads
Primary voltage
208D, 230D, 460D, 480D, 575D
Rating
660 kVA
Ratings
7.5 to 660 kVA
Secondary connection
Wye-N
Secondary termination (std)
Mounting pads
Secondary voltage
240Y/139
Seismic compliance
IBC 2018 (Sds=2.0, z/h=0, lp=1.5)
Sound level
62 dBA (NEMA ST-20)
Standard kVA
660
Temperature rise
150°C
Thermal protective device
Normally closed (all coils) thermostats with 200°C setpoint, typically built to order
Vector configuration
Dyn1 (-30°)
HPS Drive Isolation Transformers, are designed to meet the rugged demands of both AC and DC variable speed drives and also provide the required voltage change.
The separate primary and secondary windings provide electrical isolation between the incoming line and the SCR load. The windings are designed to withstand overcurrent of 150% of the rated load for 60 seconds or 200% of the rated load for 30 seconds.
Drive Isolation Transformers are sized to match standard motor horsepower and voltage ratings.
Standard sizes range from 5 to 600 HP in six standard voltages.
Great price and fast shipping
Verified · SKU 2835662MRO exceeded expectations, with a great price and fast shipping. Read more
Shipped fast, great product
Verified · SKU 2836246Found these at a good price, shipped very fast. Nice quality. Read more
Hps c1f002wes
Verified · SKU 2835661I was looking for a 2KVA isolation transformer, and I found it at MROSupply! Delivery was quick, and once I installed it everything worked as expected. I highly recommend this product to customers looking for a similar transformer. Read more
Brand
RAB Lighting
Model
ALEDXL4TNB
Brand
Goulds
Model
2SVB2D2B
Brand
Timken
Model
24801-2127
Brand
Te-Co
Model
53509
Brand
Dormer Pramet
Model
5983821
Brand
Timken
Model
29602-6962
Brand
Dodge
Model
298179
Brand
Dodge
Model
NSTU-SC-105