We never sell your data to third parties
ABB MS325-20.0 Manual Motor Starter | 1SAM150000R1013
MODEL MS325-20.0
Item no longer available through MROSupply.com
Returnable: Yes
440 V DC
440 V DC
Actuator type
Rotary Handle
Ambient air temperature compensation
Yes
Ampere rating UL/CSA
20 A
ATEX certificate
1SAA918000-3903
BV certificate
1SAA918000-0204
CB certificate
1SAA918000-2002
CCC certificate
1SAA918000-3806
Connecting capacity main circuit UL/CSA
Flexible 1/2x 14-8 AWG Stranded 1/2x 14-8 AWG
Contact position indication
ON / OFF
Conventional free-air thermal current (Ith)
Main Circuit 20 A
Country of Origin
Czech Republic (CZ)
cUL certificate
cUL_E137861 cUL_E345003
Current
20 A
Data sheet, technical information
2CDC131046D0201
Data sheet, technical information (Part 2)
1SAM100513F0013
Declaration of conformity - CE
1SAD938513-0003
Degree of protection
IP20
DNV certificate
1SAA918000-0305
eClass
7.0 27370401
Electrical durability
50000 cycle
ETIM 4
EC000074 - Motor protective circuit-breaker
ETIM 5
EC000074 - Motor protective circuit-breaker
ETIM 6
EC000074 - Motor protection circuit-breaker
GL certificate
1SAA918000-0403
GOST certificate
1SAA918000-2703
Lead time
14 day(s)
LR certificate
1SAA918000-0503
Made to order
No
Max operating altitude permissible
2000 m
Maximum operating voltage UL/CSA
Main Circuit 600 V AC
Mechanical durability
100000 cycle
Mounting position
Position 1 to 6
Number of poles
3
Object classification code
F
Poles
3
Pollution degree
3
Power loss
at Rated Operating Conditions per Pole 1.0 ... 1.6 W
Product sales status
Inactive
Quote only
No
Rated frequency
Main Circuit 50 Hz Main Circuit 60 Hz
Rated impulse withstand voltage (U imp)
Main Circuit 6 kV
Rated instantaneous short-circuit current setting (Ii)
300 A
Rated insulation voltage (Ui)
690 V
Rated operational current (Ie)
20 A
Rated operational current AC-3 (Ie)
20 A
Rated operational power AC-3 (Pe)
(400 V) Three Phase 7.5 kW
Rated operational voltage
Main Circuit 690 V AC Main Circuit 440 V DC
Rated service short-circuit breaking capacity (Ics)
(230 V AC) 100 kA (400 V AC) 55 kA (440 V AC) 35 kA (500 V AC) 22 kA (690 V AC) 3.5 kA
Rated ultimate short-circuit breaking capacity (Icu)
(230 V AC) 100 kA (400 V AC) 55 kA (440 V AC) 35 kA (500 V AC) 22 kA (690 V AC) 3.5 kA
Recommended screw driver
M3.5 Pozidriv 2
Resistance to shock acc. to IEC 60068-2-27
11 ms Pulse 15g
Resistance to vibrations acc. to IEC 60068-2-6
5g / 10 ... 150 Hz
RINA certificate
1SAA918000-0803
RMRS certificate
1SAA918000-0703
RoHS information
1SAA918001-4401
RoHS status
Following EU Directive 2002/95/EC August 18, 2005 and amendment
Setting range
16 ... 20 A
Standards
IEC/EN 60947-1 IEC/EN 60947-2 IEC/EN 60947-4-1 UL 60947-1 UL 60947-4-1
Tightening torque
Main Circuit 1.4 Nm
Tightening torque UL/CSA
Auxiliary Circuit 7 inlb Main Circuit 14 inlb
UL certificate
UL_E137861 UL_E345003
Voltage
690 V AC
Wire stripping length
Auxiliary Circuit 8 mm Main Circuit 10 mm
Ambient air temperature: Around the Enclosure 0 ... +40 C Operation -25 ... +50 C Operation Compensated -25 ... +50 C Storage -50 ... +80 C
Connecting capacity main circuit: Flexible with Ferrule 1/2x 0.75 ... 4 mm Flexible with Insulated Ferrule 1/2x 0.75 ... 4 mm Flexible 1/2x 1 ... 6 mm Rigid 1/2x 1 ... 6 mm
Horsepower rating UL/CSA: (220 ... 240 V AC) Three Phase 5 Hp (440 ... 480 V AC) Three Phase 10 Hp (550 ... 600 V AC) Three Phase 15 Hp
Mounting on DIN rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Brand
Thomson Linear
Model
511U45E2CG1
Brand
Flexco
Model
38111
Brand
Fibox
Model
AR16148CHLTM
Brand
Drillco
Model
91CT152
Brand
Thomson Linear
Model
SN2516X
Brand
Orbit Industries
Model
OF533
Brand
Timken
Model
39PP
Brand
Wiegmann
Model
N412423610C