N62E-84

Image for Illustration purposes only. Actual product may vary

View in markdown

ABB N62E-84 Contactor Relay | N62E-84

MODEL N62E-84

BRAND

ABB

SKU

6151755

UOM

each

Item no longer available through MROSupply.com

Typically Ships in: 1 day

Returnable: Yes

BV certificate

BV_2634H09651C0

CB certificate

CB_FR_602227B

CCC certificate

CCC_2003010304088236

Climatic withstand

acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II

Coil operating limits

(acc. to IEC 60947-5-1) 0.85 ... 1.1 x Uc (at 55 C) C

Connecting capacity auxiliary circuit

Flexible with Cable End 0.75 ... 2.5 mm Rigid Cable 1 ... 4 mm

Conventional free-air thermal current (Ith)

acc. to IEC 60947-5-1, q = 40 C 16 A

CSA certificate

CSA_1041746

cUL certificate

UL_110105E48139A

Data sheet, technical information

1SBC100122C0202_Ch03

Declaration of conformity - CE

1SBD250808U1000

Degree of protection

acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20

DNV certificate

DNV-GL_TAE00000TY

ETIM 4

EC000196 - Contactor relay

ETIM 5

EC000196 - Contactor relay

ETIM 6

EC000196 - Contactor relay

GL certificate

DNV-GL_TAE00000TY

GOST certificate

GOST_POCCFRME01B03022

LR certificate

LRS_9830010E2

Max mechanical switching frequency

6000 cycles per hour

Max operating altitude permissible

3000 m

Mechanical durability

> 20 million

Number of auxiliary contacts NC

2

Number of auxiliary contacts NO

4

Object classification code

K

Rated control circuit voltage (Uc)

50 Hz 110 V 60 Hz 110 120 V

Rated frequency

Supply Circuit 50 Hz Supply Circuit 60 Hz

Rated impulse withstand voltage (U imp)

8 kV

Rated insulation voltage (Ui)

acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V acc. to UL/CSA 600 V

Rated operational current AC-15 (Ie)

(220 / 240 V) 4 A (24 / 127 V) 6 A (380 / 440 V) 3 A (500 V) 2 A (690 V) 2 A

Rated operational current DC-13 (Ie)

(125 V) 0.55 / 69 A (24 V) 6 / 144 A (250 V) 0.3 / 75 A (48 V) 2.8 / 134 A (72 V) 1 / 72 A

Rated operational voltage

Main Circuit 690 V

Rated short-time withstand current (Icw)

for 0.1 s 140 A for 1 s 100 A

RINA certificate

RINA_ELE128713XG002

RMRS certificate

RMRS_0507015250

RoHS information

1SBD350056R1000

RoHS status

Following EU Directive 2002/95/EC August 18, 2005 and amendment

Short-circuit protective devices

gG Type Fuses 10 A

Terminal type

Screw terminals

UL certificate

UL_110105E48139A

  • N... Contactor Relays Are Used For Switching Auxiliary Circuits And Control Circuits - Poles: 8-Pole Contactor Relays (Mechanically Linked Contact Elements Available) The Width Of 8-Pole Devices Is Identical To That Of 4-Pole Devices Only The Depth Is Increased - Control Circuit: Ac Operated With Laminated Magnet Circuit - Accessories: A Wide Range Of Accessories Is Available.
    Only The Depth Is Increased
    - Control Circuit: Ac Operated With Laminated Magnet Circuit
    - Accessories: A Wide Range Of Accessories Is Available.

Standards: Devices complying with international standards IEC 947-5-1 / 947-4-1 and European standards EN 60 947-5-1 / 60 947-4-1. Electromagnetic compatibility (EMC) according to amendment A11 to IEC 947-1; EN 60 947-1 and amendment 2 to IEC 947-4-1

Ambient air temperature: Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 C Near Contactor for Operation in Free Air (Uc) -40 ... +70 C Close to Contactor for Storage -60 ... +80 C

Coil consumption: Pull-in at Max. Rated Control Circuit Voltage 50 Hz 70 VA Pull-in at Max. Rated Control Circuit Voltage 60 Hz 80 VA Holding at Max. Rated Control Circuit Voltage 60 Hz 8 VA Holding at Max. Rated Control Circuit Voltage 60 Hz 2 W Holding at Max. Rated Control Circuit Voltage 50 Hz 8 VA Holding at Max. Rated Control Circuit Voltage 50 Hz 2 W Average Holding Value 50 / 60 Hz 8 VA Average Holding Value 50 / 60 Hz 2 W Average Pull-in Value 50 Hz 74 VA Average Pull-in Value 60 Hz 70 VA

Operate time: Between Coil Energization and NO Contact Closing 10 ... 26 ms Between Coil De-energization and NO Contact Opening 4 ... 11 ms Between Coil De-energization and NC Contact Closing 9 ... 16 ms Between Coil Energization and NC Contact Opening 7 ... 21 ms

Resistance to shock acc. to IEC 60068-2-27: Shock Direction A 20 g Closed, Shock Direction B1 10 g Open, Shock Direction B1 5 g Shock Direction B2 15 g Shock Direction C1 20 g Shock Direction C2 20 g

Recently Viewed
7229844

#6067699

Brand

Pramet

Model

7229844

$22.72 Each
Free Shipping orders over $100
1995B

#2845537

Brand

Cooper Wiring

Model

1995B

$43.47 Each
Free Shipping orders over $100