We never sell your data to third parties
Meltric 28-18165 DXA1 ATEX-certified hazardous location inlet with metal housing, 20A, 120VAC, 60Hz, 1 Pole + Neutral + Ground (1P+N+G) configuration in a Size 2 frame. Switch-rated DECONTACTOR device with IP66/67 rating for dust ingress and temporary water immersion protection, suitable for Class I, Zone 2 hazardous areas requiring a motor disconnect.
MODEL 28-18165
$150.70 Each
Prices are subject to change
FREE SHIPPING ON ORDERS OVER $100
Select Quantity
Typically Ships in: 1 day
Returnable: Yes
Accessory Size
2
CSA List File
208161
CSA List Std 1
C22.2 No. 60079-0
CSA List Std 2
C22.2 No. 60079-11
CSA Listing
cCSAus
Current Interrupting Rating
CURRENT INTERRUPTING
Ex Rating Line 1
Ex de IIC T* Gb
Ex Rating Line 2
Ex tb IIIC T* Db
Ex Rating Line 3
* -55C < Ta < +40C T6 T68C
Ex Rating Line 4
* -55C < Ta < +60C T5 T88C
Frequency
60 Hz
Hazardous Location Class Div Dust Rating
Class II Div 2 Gr E, F, G
Hazardous Location Class Div Gas Rating
Class I Div 2 Gr A, B, C, D
Hazardous Location Zone Dust Rating Line 1
Zone 21 AEx tD T* Db
Hazardous Location Zone Dust Rating Line 2
*-55C
Hazardous Location Zone Gas Rating Line 1
Class I Zone 1 AEx de IIC T* Gb
Hazardous Location Zone Gas Rating Line 2
*-55C
HP
0.75
Impact Rating
IK10
Keying Position
16
Load Break Abnormal Overload
30 A
Load Break Normal Operation
20 A
Material
METAL
Maximum Operating Temperature-C
60C
Maximum Operating Temperature-F
140F
Metal Type
ALUMINUM PAINTED
Minimum Operating Temperature-C
-55C
Minimum Operating Temperature-F
-67F
Number of Notch Pos
24
Phase Condenser Strip Length
1/2 IN OR 13 MM
Phase Term Tightening Torque
7.1 IN-LBS / 0.8 N-M
Phase Term Type
SCREW TERMINAL
Phase Term Wire Cap Max THHN
10 AWG
Phase Term Wire Cap Min THHN
16 AWG
Primary IP Rating
66/67
Prod Wire Temperature Rating
60C
Product Color
BLACK
Rated Current
20 A
Rated Voltage
120 VAC
Short Circuit Rating
25 kA - CLOSE & WITHSTAND
Short Circuit Rating Fusing
25 kA 30 A (400%) RK1 NTD
Voltage Color Code
YELLOW