Recommended copper wire gage and transformer size for Three Phase - 230 & 460V - electrical motors
All wiring and electrical connections should comply with the National Electrical Code (NEC) and with local codes and practices.
Wire Gage (AWG) | |||||||
---|---|---|---|---|---|---|---|
Transformer | Distance - Motor to Transformer (Feet) | ||||||
HP | Volts | kVA | 100 | 150 | 200 | 300 | 500 |
1.5 | 230 | 3 | 12 | 12 | 12 | 12 | 10 |
2 | 460 | 3 | 12 | 12 | 12 | 12 | 12 |
3 | 230 | 3 | 12 | 12 | 12 | 10 | 8 |
2 | 460 | 3 | 12 | 12 | 12 | 12 | 12 |
3 | 230 | 5 | 12 | 10 | 10 | 8 | 6 |
3 | 460 | 5 | 12 | 12 | 12 | 12 | 10 |
5 | 230 | 7.5 | 10 | 8 | 8 | 6 | 4 |
5 | 460 | 7.5 | 12 | 12 | 12 | 10 | 8 |
7.5 | 230 | 10 | 8 | 6 | 6 | 4 | 2 |
7.5 | 460 | 10 | 12 | 12 | 12 | 10 | 8 |
10 | 230 | 15 | 6 | 4 | 4 | 4 | 1 |
10 | 460 | 15 | 12 | 12 | 12 | 10 | 8 |
15 | 230 | 20 | 4 | 4 | 4 | 2 | 0 |
15 | 460 | 20 | 12 | 10 | 10 | 8 | 6 |
20 | 230 | 1) | 4 | 2 | 2 | 1 | 0 |
20 | 460 | 1) | 10 | 8 | 8 | 6 | 4 |
25 | 230 | 1) | 2 | 2 | 2 | 0 | 0 |
30 | 230 | 1) | 2 | 1 | 1 | 0 | 0 |
30 | 460 | 1) | 8 | 6 | 6 | 4 | 2 |
40 | 230 | 1) | 1 | 0 | 0 | 0 | 0 |
50 | 230 | 1) | 1 | 0 | 0 | 0 | 0 |
50 | 460 | 1) | 4 | 4 | 2 | 2 | 0 |
30 | 230 | 1) | 1 | 0 | 0 | 0 | 0 |
60 | 460 | 1) | 4 | 2 | 2 | 0 | 0 |
75 | 230 | 1) | 0 | 0 | 0 | 0 | 0 |
75 | 460 | 1) | 4 | 2 | 2 | 0 | 0 |
1) The local power company should be consulted
- 1 ft (foot) = 0.3048 m
If undersized wire is used between the motor and the power source, the starting and load carrying cap abilities of the motor will be limited.