Accuracy (in the measuring range)
± 5 % MEW; (Q > 1 l/min; 20...70 °C Medium temperature)
Accuracy (K)
3 K (25°C; Q > 1 l / min)
Accuracy [K]
3 K (25°C; Q > 1 l/min)
Ambient Temperature (°C)
0...60
Ambient temperature [°C]
0...60
Analog Current Output (Ma)
4...20
Analog current output [mA]
4...20
Communication Interface
IO-Link
Connector
1 x M12; coding: A; Contacts: 4, gold-plated
Current Consumption (Ma)
< 50
Current consumption [mA]
< 50
Damping for The Analog Output dAA (S)
0...5
Damping for the analog output dAA [s]
0...5
Damping Process Value dAP (S)
0...5
Damping process value dAP [s]
0...5
Display Unit
6 x LED, green
Dynamic Response T05 / T09 (S)
T09 = 120 (Q > 1 l / min)
Dynamic response T05 / T09 [s]
T09 = 120 (Q > 1 l/min)
File Number UL
E174189
Frequency At The End Point FRP (Hz)
10...10000
Frequency at the end point FRP [Hz]
10...10000
Frequency of The Output (Hz)
0...10000
Frequency of the output [Hz]
0...10000
In Steps of (Hz)
10
In steps of [Hz]
10
In steps of [s]
0.1
IO-Link Revision
1.1
Max. load [Ω]
500
Max. voltage drop switching output DC [V]
2
Maximum Current Load Per Output (Ma)
150
Maximum Load (Ω)
500
Maximum Voltage Drop Switching Output DC (V)
2
Measured Values
alphanumeric display, red / green alternating indication 4-digit
Measuring Dynamics
1:50
Media
Liquids; oil (viscosity 100 mm² / s at 40° C)
Medium Temperature (°C)
-10...100
Medium temperature [°C]
-10...100
Min. process cycle time [ms]
3.2
Minimum Process Cycle Time (Ms)
3.2
Operating Voltage (V)
18...30 DC
Operating voltage [V]
18...30 DC; (to SELV/PELV)
Output signal
Switching signal; analog signal; frequency signal; IO-Link
Overload Protection
Yes
Pack quantity
1 pcs.
Power-on Delay Time (S)
< 3
Power-on delay time [s]
< 3
Pressure Equipment Directive
Sound Engineering Practice
Process Connection
Threaded Connection G 3 / 4 Internal Thread
Process data analog
2
Process data binary
2
Programming
alphanumeric display, 4-digit
Protection
IP 65; IP 67
Protection Class
III
Repeatability
± 1 % MEW
Required master port class
A
Response Time (S)
0.01
Response time [s]
0.01
Reverse Polarity Protection
Yes
SDCI Standard
IEC 61131-9 CDV
Short-circuit Protection
Yes
SIO mode
Yes
Special feature
Gold-plated contacts
Storage Temperature (°C)
-15...80
Storage temperature [°C]
-15...80
Switching Cycles Mechanical
10 million
Switching Status
2 x LED, yellow
Temperature Drift
0, 029 °C / K
Total Number of Outputs
2
Transmission type
COM2 (38, 4 kBaud)
- Fast flow or temperature changes do not affect the measurement
- High measurement dynamics reduces type versions
- No inlet and output pipe lengths required
- Specifically adjusted to oil for optimum measurement results
PLCs have evolved over the years to become crucial components for driving industrial automation. This post provides insights into the PLCs to help you understand how they work. Remember that you need to pick the right PLC for your system and ensure it is installed by an expert for proper performance.
Read MoreWhen selecting a PLC for industrial application, it is prudent to consider your system requirements and targeted control. It is also prudent to work with a technical expert and only acquire the PLC that guarantees better results.
Read MoreBrand
IFM
Model
EVF775
Brand
Walter
Model
10A123
Brand
Walter
Model
05A015
Brand
Walter
Model
6998
Brand
Flowtrend
Model
2101722
Brand
Walter
Model
9504-50E
Brand
Hubbell Wiring
Model
DR20STRTR
Brand
Walter
Model
48M510