Adjustment of The Switch Point
Pushbuttons
Ambient Temperature (°C)
-25...80
Ambient temperature [°C]
-25...80
Connector
1 x M12; coding: A
Current Consumption (Ma)
< 60
Current consumption [mA]
< 60
Dimensions (mm)
Ø 50 / L = 113
Dimensions [mm]
Ø 50 / L = 113
Electrical Design
PNP
Greatest Sensitivity (Cm/S)
3...100
Greatest sensitivity [cm/s]
3...100
Housing
Tubular
Hysteresis (Cm/S)
2...5
Hysteresis [cm/s]
2...5; (for water 5...100 cm/s; 25 °C; Factory setting)
Installation Length EL (mm)
45
Installation length EL [mm]
45
Materials (Wetted Parts)
stainless steel (1.4404 / 316L); O-ring: FKM 80 Shore A
Max. temperature gradient of medium [K/min]
300
Max. voltage drop switching output DC [V]
2.5
Maximum Temperature Gradient of Medium (K/Min)
300
Maximum Voltage Drop Switching Output DC (V)
2.5
Media
Liquids
Medium Temperature (°C)
-15...70
Medium temperature [°C]
-15...70
MTTF (Years)
267
MTTF [years]
267
Number of Digital Outputs
2
Number of inputs and outputs
Number of digital outputs: 2
Operating Voltage (V)
24 DC
Operating voltage [V]
24 DC; (18...32 DC)
Output Function
Normally Open / Closed
Output Signal
Switching Signal
Overload Protection
Yes
Pack quantity
1 pcs.
Permanent Current Rating of Switching Output DC (Ma)
250
Permanent current rating of switching output DC [mA]
250
Power-on Delay Time (S)
10
Power-on delay time [s]
10
Probe Diameter (mm)
8.2
Probe diameter [mm]
8.2
Probe Length L (mm)
45
Probe length L [mm]
45
Process Connection
threaded connection M18 x 1, 5 Internal thread
Protection
IP 67
Protection Class
III
Repeatability (% of Sr)
1...5
Repeatability [% of Sr]
1...5
Response Time (S)
1...10
Response time [s]
1...10
Reverse Polarity Protection
Yes
Setting Range (Cm/S)
3...300
Setting range [cm/s]
3...300
Short-circuit Protection
Yes
Storage Temperature (°C)
-25...100
Storage temperature [°C]
-25...100
Switch Point Accuracy (Cm/S)
± 10
Switch point accuracy [cm/s]
± 10; (for water 5...100 cm/s; 25 °C; Factory setting)
Temperature Drift (Cm/S X 1/K)
0.1
Temperature drift [cm/s x 1/K]
0.1; (for water 5...100 cm/s; 15...70 °C)
Total Number of Outputs
2
Type of Short-circuit Protection
Yes (Non-latching)
- Reliable monitoring of liquids and gases in pipes
- Variable process connection using adapters
- Easy setting of the switch points for quick set-up
- Robust stainless steel housing for use in harsh industrial environments
- LED bar graph for indication of switch point and flow
PLCs have evolved over the years to become crucial components for driving industrial automation. This post provides insights into the PLCs to help you understand how they work. Remember that you need to pick the right PLC for your system and ensure it is installed by an expert for proper performance.
Read MoreWhen selecting a PLC for industrial application, it is prudent to consider your system requirements and targeted control. It is also prudent to work with a technical expert and only acquire the PLC that guarantees better results.
Read MoreBrand
Walter
Model
9920-03B
Brand
IFM
Model
IFM205
Brand
RAB Lighting
Model
A22-2T320/480
Brand
Walter
Model
9904-D
Brand
Dichtomatik
Model
75011114
Brand
Dodge
Model
P2B-SC-45M-LL
Brand
FEIN
Model
30707547010