Returnable: Yes
Accuracy (In The Measuring Range)
Water
Accuracy [K]
± 0, 3 ± 0, 005 x T
Ambient Temperature (°C)
-15...85
Ambient temperature [°C]
-15...85
Analog Current Output (Ma)
4...20
Analog current output [mA]
4...20
Cavitation
P(absolute) discharge / P(difference) > 5.5 to avoid cavitation
Connector
1 x M12; coding: A; Contacts: 4, gold-plated
Current Consumption (Ma)
< 5
Current consumption [mA]
< 5
Dimensions (mm)
120 x 41.91 x 68
Dimensions [mm]
120 x 41.91 x 68
Dp
[mbar] = Pressure loss
Dynamic Response T05 / T09 (S)
< 10 / < 30
Dynamic response T05 / T09 [s]
< 10 / < 30
File Number UL
E364788
Glycol Solutions (35%)
2 > v < 6 cSt: ± 5% MEW / 6 > v < 15 cSt: ± 10% MEW
Housing
Rectangular
Installation
Connection to pipe by means of an adapter
Internal Heating Temperature Probe
1 K / mW
Material
Housing: PPS 40% glass fiber; electronics: PC 10% glass fiber
Materials (Wetted Parts)
sensor: PPSU; Pipe section: PPS 40% glass fiber; sealing: EPDM
Max. load [Ω]
< (Ub - 8 V) / 20 mA; Ub = 24 V: 800
Maximum Load (Ω)
< (Ub - 8 V) / 20 mA; Ub = 24 V: 800
Measuring Element
1 x Pt 1000
Measuring Principle
Vortex
Measuring Range (°C)
-15...125
Measuring range [°C]
-15...125
Media
Ultra-pure Water; Water; Glycol Solutions; Coolants
Medium Temperature (°C)
-15...125
Medium temperature [°C]
-15...125
Min. insulation resistance [MΩ]
100; (500 V DC)
Minimum Insulation Resistance (MΩ)
100
MTTF (Years)
395.9
MTTF [years]
396
Number of Analog Outputs
1
Number of inputs and outputs
Number of analog outputs: 1
Operating Voltage (V)
8...33 DC
Operating voltage [V]
8...33 DC
Output Signal
Analog Signal
P
[bar] = pressure
Pack quantity
1 pcs.
Power-on Delay Time (S)
< 2
Power-on delay time [s]
< 2
Process Connection
threaded connection G 1 1 / 4 external thread DN25
Protection
IP 65
Protection Class
III
Repeatability
0, 2
Response Time (S)
0.38
Response time [s]
0.38; (T09)
Special feature
Gold-plated contacts
Storage Temperature (°C)
-40...85
Storage temperature [°C]
-40...85
T
[°C] = temperature
Tightening Torque (Nm)
15
Tightening torque [Nm]
15
Total Number of Outputs
1
V =
kinematische Viskosität
Water
Q < 50 % MEW: < 1 % MEW / Q > 50 % MEW: < 2 % MW
- Reliable detection of flow and medium temperature
- Precise linearized analog output
- Suitable for ultrapure water, water and water-based media
- Durable and robust thanks to hydrolysis-resistant plastic
- High precision of flow and temperature monitoring
PLCs have evolved over the years to become crucial components for driving industrial automation. This post provides insights into the PLCs to help you understand how they work. Remember that you need to pick the right PLC for your system and ensure it is installed by an expert for proper performance.
Read MoreWhen selecting a PLC for industrial application, it is prudent to consider your system requirements and targeted control. It is also prudent to work with a technical expert and only acquire the PLC that guarantees better results.
Read MoreBrand
Timken
Model
21158-0319
Brand
Cooper Wiring
Model
PJ703W
Brand
NTN Bearing
Model
50TSK39
Brand
Timken
Model
22987-6846
Brand
Regal Cutting Tools
Model
050374AM
Brand
SKF Seals
Model
14383
Brand
PTI
Model
28B-2-13B