We never sell your data to third parties
IFM LR2050 LR0000B-ER34AKSKG/US Continuous level sensor (guided wave radar)
MODEL LR2050
$984.72 Each
Prices are subject to change
FREE SHIPPING ON ORDERS OVER $100
Select Quantity
Returnable: Yes
Active Range A (mm)
L-40 (L-60)
Active range A [mm]
L-40 (L-60); (when set to oil and oil based media)
Ambient Temperature (°C)
-40...80
Ambient temperature [°C]
-40...80
Analog Current Output (Ma)
4...20, invertible
Analog current output [mA]
4...20, invertible; (scalable)
Communication Interface
IO-Link
Connector
1 x M12; coding: A; Contacts: gold-plated
Current Consumption (Ma)
< 50
Current consumption [mA]
< 50
Dimensions (mm)
Ø 50 / L = 119
Dimensions [mm]
Ø 50 / L = 119
Display Unit
3 x LED, green
Electrical Design
PNP / NPN
Full Signal (Current) (Ma)
20
Full signal (current) [mA]
20
Hysteresis (mm)
> 5
Hysteresis [mm]
> 5
In Steps of (mm)
1
In steps of [mm]
1
Inactive Range I1 / I2 (mm)
30 / 10 (30)
Inactive range I1 / I2 [mm]
30 / 10 (30); (when set to oil and oil based media)
IO-Link Revision
1.1
Level
alphanumeric display, 4-digit
Material
stainless steel (1.4404 / 316L); PEI; PFA; PBT; FKM
Materials (Wetted Parts)
stainless steel (1.4404 / 316L); stainless steel (1.4435 / 316L); PTFE; FKM
MAWP (for Applications According To CRN) (Bar)
16
MAWP (for applications according to CRN) [bar]
16
Max. load [Ω]
500
Max. voltage drop switching output DC [V]
2.5
Maximum Load (Ω)
500
Maximum Voltage Drop Switching Output DC (V)
2.5
Measuring Error (mm)
± 7
Measuring error [mm]
± 7
Measuring Principle
Guided Wave Radar
Media
Liquids
Min. process cycle time [ms]
2.3
Minimum Process Cycle Time (Ms)
2.3
MTTF (Years)
216
MTTF [years]
216
Number of Analog Outputs
1
Number of Digital Outputs
1
Number of inputs and outputs
Number of digital outputs: 1; Number of analog outputs: 1
Offset Error (mm)
5
Offset error [mm]
5
Operating Voltage (V)
18...30 DC
Operating voltage [V]
18...30 DC
Output Function
Normally Open / Closed
Output Signal
switching signal; analog signal; IO-Link
Overload Protection
Yes
Pack quantity
1 pcs.
Parameter Setting
alphanumeric display, 4-digit
Permanent Current Rating of Switching Output DC (Ma)
150; (200 (...60 °C))
Permanent current rating of switching output DC [mA]
150; (200 (...60 °C))
Power-on Delay Time (S)
< 3
Power-on delay time [s]
< 3
Probe Length L (mm)
150...2000
Probe length L [mm]
150...2000
Process Connection
Threaded Connection G 3 / 4 External Thread
Process data analog
1
Process data binary
2
Process Temperature (°C)
-20...100
Process temperature [°C]
-20...100; (see note under remarks)
Protection
IP 68; IP 69K
Protection Class
III
Recommended media
Water; water-based media; oils; oil-based media
Required master port class
A
Reset Point Rp (mm)
10... L-35
Reset point rP [mm]
10... L-35
Resolution (mm)
1
Resolution [mm]
1
Reverse Polarity Protection
Yes
Sampling Rate (Hz)
4
Sampling rate [Hz]
4
SDCI Standard
IEC 61131-9
Set Point SP (mm)
15...L-30
Set point SP [mm]
15...L-30
Short-circuit Protection
Yes
SIO mode
Yes
Special feature
Gold-plated contacts
Storage Temperature (°C)
-40...100
Storage temperature [°C]
-40...100
Switching Status
2 x LED, yellow
Temperature Drift Per 10 K
± 0.2 %
Total Number of Outputs
2
Transmission type
COM2 (38, 4 kBaud)
Type of Short-circuit Protection
Yes (Non-latching)
Zero Signal (Current) (Ma)
4
Zero signal (current) [mA]
4.0
- For the reliable level control in tanks and containers
- Suitable for water, oils and coolants
- Clearly visible numerical display
- Modular system consisting of evaluation unit and probe
- Probes may be cut to length for application flexibility
PLCs have evolved over the years to become crucial components for driving industrial automation. This post provides insights into the PLCs to help you understand how they work. Remember that you need to pick the right PLC for your system and ensure it is installed by an expert for proper performance.
Read MoreWhen selecting a PLC for industrial application, it is prudent to consider your system requirements and targeted control. It is also prudent to work with a technical expert and only acquire the PLC that guarantees better results.
Read MoreBrand
Dodge
Model
H3C18S00616
Brand
U.S.Tsubaki
Model
60B38F-1C
Brand
Timken
Model
21086-2804
Brand
Dormer Pramet
Model
5973156
Brand
FLIR
Model
MR13