Accuracy (K)
± 2.5 K + (0.045 x (ambient temperature - medium temperature))
Ambient Temperature (°C)
-25...90
Ambient temperature [°C]
-25...90
Analog Current Output (Ma)
4...20
Analog current output [mA]
4...20; (scalable; 1:10)
Characteristics Deviation (% of The Span)
< ± 0, 5
Communication Interface
IO-Link
Connector
1 x M12; coding: A; Contacts: 4, gold-plated
Current Consumption (Ma)
< 30
Current consumption [mA]
3.5...21.5
Damping for The Analog Output dAA (S)
0...99.99
Damping for the analog output dAA [s]
0...99.99
Damping Process Value dAP (S)
0...99.99
Damping process value dAP [s]
0...99.99
Device Status
4
Dimensions (mm)
Ø 30 / L = 63
Dimensions [mm]
Ø 30 / L = 63
Display Unit
2 LED, green
Dynamic Response T05 / T09 (S)
< 10 / <45
Dynamic response T05 / T09 [s]
< 10 / <45; (DIN EN 60751 water; > 0, 9 m/s)
Embedded Software Included
Yes
File Number UL
E174189
Housing
Tubular
Hysteresis Deviation (% of The Span)
< ± 0, 15
Hysteresis deviation [% of the span]
< ± 0, 15; (Turn down 1:1)
Integrated Watchdog
Yes
IO-Link Functions (Acyclical)
Application Specific Tag; Internal Temperature
IO-Link Resolution Pressure (Mbar)
0.5
IO-Link resolution pressure [mbar]
0.5
IO-Link Resolution Temperature (K)
0.2
IO-Link resolution temperature [K]
0.2
IO-Link Revision
1.1
Linearity Deviation (% of The Span)
< ± 0, 15
Linearity deviation [% of the span]
< ± 0, 15; (Turn down 1:1)
Long-term Stability (% of The Span)
< ± 0, 1
Long-term stability [% of the span]
< ± 0, 1; (Turn down 1:1; per year)
Material
stainless steel (1.4435 / 316L); stainless steel (1.4404 / 316L); PA; PTFE; FKM
Max. load [Ω]
(Ub - 9, 6 V) / 21, 5 mA; 670 Ω (Ub = 24 V)
Maximum Load (Ω)
(Ub - 9, 6 V) / 21, 5 mA; 670 Ω (Ub = 24 V)
Measuring Element
Ceramic-capacitive Pressure Measuring Cell
Medium Temperature (°C)
-15...110
Min. insulation resistance [MΩ]
100; (500 V DC)
Min. pressure cycles
100 million
Min. process cycle time [ms]
3.5
Minimum Insulation Resistance (MΩ)
100
Minimum Pressure Cycles
100 million
Minimum Process Cycle Time (Ms)
3.5
MTTF (Years)
407
MTTF [years]
407
NO Dead Space
Yes
Number of Analog Outputs
1
Number of Digital Outputs
1
Number of inputs and outputs
Number of digital outputs: 1; Number of analog outputs: 1
Operating Voltage (V)
9.6...30 DC
Operating voltage [V]
9.6...30 DC
Output Signal
analog signal; IO-Link
Overload Protection
Yes
Pack quantity
1 pcs.
Power-on Delay Time (S)
< 0.5
Power-on delay time [s]
< 1
Pressure
16
Process Connection
Threaded Connection G 1 / 2 External Thread
Protection
IP 67; IP 68; IP 69
Protection Class
III
Repeatability (% of The Span)
< ± 0, 1
Required master port class
A; (when pin 2 not connected: B)
Reverse Polarity Protection
Yes
SDCI Standard
IEC 61131-9
Short-circuit Proof
Yes
SIO mode
No
Special feature
Gold-plated contacts
Step Response Time Analog Output (Ms)
3
Step response time analog output [ms]
12
Storage Temperature (°C)
-40...100
Storage temperature [°C]
-40...100
Temperature
16
Temperature Coefficient Span (% of The Span / 10 K)
< ± 0, 1 (-25...85 °C) < ± 0, 3 (85...110 °C)
Temperature coefficient span [% of the span / 10 K]
< ± 0, 1 (-25...85 °C) < ± 0, 3 (85...110 °C)
Temperature Coefficient Zero Point (% of The Span / 10 K)
< ± 0, 1 (-25...85 °C) < ± 0, 3 (85...110 °C)
Temperature coefficient zero point [% of the span / 10 K]
< ± 0, 1 (-25...85 °C) < ± 0, 3 (85...110 °C)
Temperature Monitoring
Yes
Tightening Torque (Nm)
25
Tightening torque [Nm]
25
Total Number of Outputs
2
Transmission type
COM2 (38, 4 kBaud)
Type of Pressure
Relative Pressure; Vacuum
Vacuum Resistance (Mbar)
-1000
Vacuum resistance [mbar]
-1000
Zero-point Stabilization (% of The Span)
0, 15; (IO-Link; analog output; (see operating instructions zero-point behavior))
- Robust ceramic measuring cell integrated flush in the process connection
- Insert with rear seal for standard screw fittings
- Compact and robust stainless steel housing for use where space is restricted
- Excellent repeatability and low linearity error
PLCs have evolved over the years to become crucial components for driving industrial automation. This post provides insights into the PLCs to help you understand how they work. Remember that you need to pick the right PLC for your system and ensure it is installed by an expert for proper performance.
Read MoreWhen selecting a PLC for industrial application, it is prudent to consider your system requirements and targeted control. It is also prudent to work with a technical expert and only acquire the PLC that guarantees better results.
Read MoreBrand
Dodge
Model
291352
Brand
FEIN
Model
69902182000
Brand
Walter
Model
094133
Brand
RAB Lighting
Model
GPLED78NBB/BL
Brand
IFM
Model
DV1501
Brand
Flowtrend
Model
40MPSE-1.5 #40-DSO