We never sell your data to third parties
IFM PY9060 PN-600-SE MFRKG/US/ / Pressure sensor with display
MODEL PY9060
$1,316.15 Each
Prices are subject to change
FREE SHIPPING ON ORDERS OVER $100
Select Quantity
Returnable: Yes
Ambient Temperature (°C)
5...80
Ambient temperature [°C]
5...80
Analog Current Output (Ma)
4...20
Analog current output [mA]
4...20; (scalable 1:5)
Analog Voltage Output (V)
0...10
Analog voltage output [V]
0...10; (scalable 1:5)
Characteristics Deviation (% of The Span)
< ± 1
Communication Interface
IO-Link
Connector
1 x M12; coding: A; Contacts: gold-plated
Current Consumption (Ma)
< 35
Current consumption [mA]
< 35
Damping for The Analog Output dAA (S)
0...4
Damping for the analog output dAA [s]
0...4
Damping Process Value dAP (S)
0...4
Damping process value dAP [s]
0...4
Delay Time Programmable Ds, Dr (S)
0...50
Delay time programmable dS, dr [s]
0...50
Dimensions (mm)
Ø 34 / L = 151
Dimensions [mm]
Ø 34 / L = 151
Display Unit
3 x LED, green (bar, psi, MPa)
Electrical Design
PNP / NPN
Housing
Tubular
Hysteresis Deviation (% of The Span)
< ± 0, 1
Hysteresis deviation [% of the span]
< ± 0, 1; (Turn down 1:1)
Integrated Watchdog
Yes
IO-Link Revision
1.1
Long-term Stability (% of The Span)
< ± 0, 05
Long-term stability [% of the span]
< ± 0, 05; (Turn down 1:1; per 6 months)
Materials (Wetted Parts)
Stainless Steel (1.4435 / 316L)
Max. load [Ω]
500
Max. response time analog output [ms]
3
Max. voltage drop switching output DC [V]
2
Maximum Load (Ω)
500
Maximum Response Time Analog Output (Ms)
3
Maximum Voltage Drop Switching Output DC (V)
2
Measured Values
alphanumeric display, red / green 4-digit
Measuring Element
Diaphragm Seal
Media
Liquids and Gases
Medium Temperature (°C)
5...125
Medium temperature [°C]
5...125; (150 maximum 1h)
Min. insulation resistance [MΩ]
100; (500 V DC)
Min. load resistance [Ω]
2000
Min. pressure cycles
60 million; (at 1.2 times nominal pressure)
Min. process cycle time [ms]
2.3
Minimum Insulation Resistance (MΩ)
100
Minimum Load Resistance (Ω)
2000
Minimum Pressure Cycles
60 million
Minimum Process Cycle Time (Ms)
2.3
MTTF (Years)
143
MTTF [years]
143
Number of Analog Outputs
1
Number of Digital Outputs
2
Number of inputs and outputs
Number of digital outputs: 2; Number of analog outputs: 1
Operating Voltage (V)
18...30 DC
Operating voltage [V]
18...30 DC; (to SELV/PELV)
Output Function
Normally Open / Closed
Output Signal
switching signal; analog signal; IO-Link
Overload Protection
Yes
Pack quantity
1 pcs.
Permanent Current Rating of Switching Output DC (Ma)
250
Permanent current rating of switching output DC [mA]
250
Power-on Delay Time (S)
0.3
Power-on delay time [s]
0.3
Process Connection
Homogenizer Connection
Process data analog
1
Process data binary
2
Protection
IP 67
Protection Class
III
Repeatability (% of The Span)
< ± 0, 1
Required master port class
A
Response Time (Ms)
< 1.5
Response time [ms]
< 1.5
Reverse Polarity Protection
Yes
SDCI Standard
IEC 61131-9
Short-circuit Protection
Yes
SIO mode
Yes
Special feature
Gold-plated contacts
Storage Temperature (°C)
-40...100
Storage temperature [°C]
-40...100
Switch Point Accuracy (% of The Span)
< ± 0, 4
Switch point accuracy [% of the span]
< ± 0, 4; (Turn down 1:1)
Switching Frequency DC (Hz)
< 500
Switching frequency DC [Hz]
< 500
Switching Status
2 x LED, yellow
Temperature Coefficient Span (% of The Span / 10 K)
0, 2
Temperature coefficient span [% of the span / 10 K]
0, 2; (5...80 °C)
Temperature Coefficient Zero Point (% of The Span / 10 K)
0, 2
Temperature coefficient zero point [% of the span / 10 K]
0, 2; (5...80 °C)
Total Number of Outputs
2
Transmission type
COM2 (38, 4 kBaud)
Type of Pressure
Relative Pressure
Type of Short-circuit Protection
Yes (Non-latching)
- Suited for use in homogenizer processes
- Programmable switching output with IO-Link and scalable analog output
- Red/green display for clear identification of the acceptable range
- The process connection can be rotated for optimum alignment
PLCs have evolved over the years to become crucial components for driving industrial automation. This post provides insights into the PLCs to help you understand how they work. Remember that you need to pick the right PLC for your system and ensure it is installed by an expert for proper performance.
Read MoreWhen selecting a PLC for industrial application, it is prudent to consider your system requirements and targeted control. It is also prudent to work with a technical expert and only acquire the PLC that guarantees better results.
Read MoreBrand
IFM
Model
EVF330
Brand
Berkeley
Model
BVM1-6-404
Brand
TURNER
Model
TRN HC204 20MM L3X
Brand
FEIN
Model
31998630010
Brand
Thomson Linear
Model
512U45B2ES2
Brand
Thomson Linear
Model
512S45C2V
Brand
Walter
Model
11A142