IFM PV7601 PV-250-SEN14-UFRVG/US/ / Pressure switch with IO-Link
MODEL PV7601
$205.37 Each
Prices are subject to change
FREE SHIPPING ON ORDERS OVER $100
Select Quantity
Returnable: Yes
Ambient Temperature (°C)
-40...90
Ambient temperature [°C]
-40...90
Characteristics Deviation (% of The Span)
< ± 0, 5
Communication Interface
IO-Link
Connector
1 x M12; coding: A
Current Consumption (Ma)
< 15
Current consumption [mA]
< 15
Dimensions (mm)
Ø 18.9 / L = 66.9
Dimensions [mm]
Ø 18.9 / L = 66.9
Electrical Design
PNP / NPN
Housing
Tubular
Hysteresis Deviation (% of The Span)
< ± 0, 2
Hysteresis deviation [% of the span]
< ± 0, 2
IO-Link
1, 0
IO-Link Revision
1.1
Linearity Deviation (% of The Span)
< ± 0, 1 (BFSL) / < ± 0, 2 (LS)
Linearity deviation [% of the span]
< ± 0, 1 (BFSL) / < ± 0, 2 (LS)
Long-term Stability (% of The Span)
< ± 0, 1
Long-term stability [% of the span]
< ± 0, 1; (per 6 months)
Material
stainless steel (630 / 1.4542 / 17-4 PH); stainless steel (1.4404 / 316L); PEI
Materials (Wetted Parts)
stainless steel (1.4305 / 303); stainless steel (630 / 1.4542 / 17-4 PH)
MAWP (for Applications According To CRN) (Bar)
625
MAWP (for applications according to CRN) [bar]
625
Max. voltage drop switching output DC [V]
2
Maximum Voltage Drop Switching Output DC (V)
2
Measuring Element
Metallic Thin Film Cell
Media
Liquids and Gases
Medium Temperature (°C)
-40...90
Medium temperature [°C]
-40...90
Min. insulation resistance [MΩ]
100; (500 V DC)
Min. pressure cycles
60 million; (at 1.2 times nominal pressure)
Min. process cycle time [ms]
5
Minimum Insulation Resistance (MΩ)
100
Minimum Pressure Cycles
60 million
Minimum Process Cycle Time (Ms)
5
MTTF (Years)
668
MTTF [years]
668
Number of Digital Outputs
2
Number of inputs and outputs
Number of digital outputs: 2
Operating Voltage (V)
18...30 DC
Operating voltage [V]
18...30 DC
Output Function
Normally Open / Closed
Output Signal
switching signal; IO-Link
Overload Protection
Yes
Pack quantity
1 pcs.
Permanent Current Rating of Switching Output DC (Ma)
100
Permanent current rating of switching output DC [mA]
100
Power-on Delay Time (S)
< 0.3
Power-on delay time [s]
< 0.3
Process Connection
threaded connection 1 / 4" NPT external thread Internal thread:M5
Protection
IP 67; IP 69K
Protection Class
III
Repeatability (% of The Span)
< ± 0, 05
Repeatability [% of the span]
< ± 0, 05; (with temperature fluctuations < 10 K)
Required master port class
A
Response Time (Ms)
< 3
Response time [ms]
< 3
Restrictor Element Integrated
Yes
Reverse Polarity Protection
Yes
SDCI Standard
IEC 61131-9
Short-circuit Protection
Yes
SIO mode
Yes
Storage Temperature (°C)
-40...100
Storage temperature [°C]
-40...100
Switch Point Accuracy (% of The Span)
< ± 0, 5 (nach DIN EN 61298-2)
Switch point accuracy [% of the span]
< ± 0, 5 (nach DIN EN 61298-2)
Switching Frequency DC (Hz)
< 170
Switching frequency DC [Hz]
< 170
Switching Output
1, 0
Temperature Coefficient Span (% of The Span / 10 K)
< 0, 1 (-25...90 °C) / < 0, 2 (-40...-25 °C)
Temperature coefficient span [% of the span / 10 K]
< 0, 1 (-25...90 °C) / < 0, 2 (-40...-25 °C)
Temperature Coefficient Zero Point (% of The Span / 10 K)
< 0, 1 (-25...90 °C) / < 0, 2 (-40...-25 °C)
Temperature coefficient zero point [% of the span / 10 K]
< 0, 1 (-25...90 °C) / < 0, 2 (-40...-25 °C)
Tightening Torque (Nm)
50
Total Number of Outputs
2
Transmission type
COM2 (38, 4 kBaud)
Type of Pressure
Relative Pressure
Type of Short-circuit Protection
Yes (Non-latching)
- Compact housing for use where space is restricted
- Very high overpressure and vacuum resistance
- Robust stainless steel housing with high shock and vibration resistance
- Lifespan of more than 60 million pressure cycles
- Two programmable switching outputs, one of them with IO-Link communication interface
PLCs have evolved over the years to become crucial components for driving industrial automation. This post provides insights into the PLCs to help you understand how they work. Remember that you need to pick the right PLC for your system and ensure it is installed by an expert for proper performance.
Read MoreWhen selecting a PLC for industrial application, it is prudent to consider your system requirements and targeted control. It is also prudent to work with a technical expert and only acquire the PLC that guarantees better results.
Read MoreBrand
Timken
Model
QMCW34J607SET
Brand
Walter
Model
012421
Brand
Dichtomatik
Model
75006718
Brand
U.S.Tsubaki
Model
H35B25FH
Brand
U.S.Tsubaki
Model
16B16F-1J
Brand
FEIN
Model
63134449003