We never sell your data to third parties
Baldor FPM2547TS is a 60/50 HP, 1770/1470 RPM three-phase electric motor with a NEMA 364T frame (9.00 inch shaft height). This dual-frequency motor operates at 60 Hz or 50 Hz, making it suitable for international applications. It is designed for demanding industrial use in applications such as pumps, fans, and compressors. The motor features robust construction for reliable performance in general-purpose and severe-duty environments.
MODEL FPM2547TS
Contact supplier for technical support on: 323 724 6771
Call for Pricing - 888-671-2883
Typically Ships in: 1 day
Returnable: See conditions
Ambient Temperature
40 °C
Base Indicator
Rigid
Conduit Box Material
Steel
Design Code
B
Duty Rating
CONT
Enclosure
ODP
Frame
364TS
Frame Material
Steel
HP
50
Hz
50/60
Insulation Class
F
Inverter Code
Not Inverter
Motor Standards
NEMA
Motor Weight
475
Mounting Arrangement
F1
Number of Poles
4
Overall Length
25.81 in
Phase
3
Power Factor
84
Pulley Face Code
STANDARD
RPM
1470/1770
Service Factor
1.15
Shaft Diameter
1.875IN
Shaft Ground Indicator
No Shaft Grounding
Shaft Rotation
Reversible
Speed Code
Single Speed
Synchronous RPM
1800
Voltage
190/230/380/460
60//50HP, 1770//1470RPM, 3PH, 60//50HZ, 364T
| Multiplier Symbol | FP |
|---|---|
| UPC | 781568811924 |
Specs
Output:
50.000 hp @ 50 Hz
60.000 hp @ 60 Hz
Phase:
3
Synchronous Speed:
1, 800 rpm
Frequency:
50.00 Hz
60.00 Hz
Voltage:
190 V @ 50 Hz
380 V @ 50 Hz
230 V @ 60 Hz
460 V @ 60 Hz
Frame Material:
Steel
Frame:
364TS
Brand:
Baldor-Reliance
Agency Approvals:
CSA
CSA EEV
UL
UR
Ambient Temperature:
40 °C
Auxillary Box:
No Auxillary Box
Auxillary Box Lead Termination:
None
Base Indicator:
Rigid
Bearing Grease Type:
POLYREX EM (-20F +300F)
Blower:
None
Current:
144.0 A @ 190 V
144.0 A @ 230 V
72.0 A @ 380 V
72.0 A @ 460 V
Design Code:
B
Drip Cover:
No Drip Cover
Duty Rating:
CONT
Efficiency @ 100% Load:
93.6%
Electrically Isolated Bearing:
Not Electrically Isolated
Feedback Device:
No feedback
Front Face Code:
Standard
Front Shaft Indicator:
None
Heater Indicator:
No heater
High Voltage Full Load Amps:
72.0 A
Insulation Class:
F
Inverter Code:
Not inverter
KVA Code:
F
Lifting Lugs:
Standard Lifting Lugs
Locked Bearing Indicator:
Locked Bearing
Motor Lead Exit:
KO Box
Motor Lead Quantity/Wire Size:
12 @ 8 AWG
Motor Lead Termination:
Flying Leads
Motor Standards:
NEMA
Motor Type:
4252M
Number of Poles:
4
Overall Length:
25.81 in
Power Factor:
84
Product Family:
FIRE PUMP MOTOR
Pulley End Bearing Type:
Ball
Pulley Face Code:
Standard
Pulley Shaft Indicator:
Standard
Rodent Screen:
None
Service Factor:
1.15
Shaft Diameter:
1.875 in
Shaft Extension Location:
Pulley End
Shaft Ground Indicator:
No Shaft Grounding
Shaft Rotation:
Reversible
Shaft Slinger Indicator:
No Slinger
Speed:
1, 770 rpm
1, 470 rpm
Speed Code:
Single Speed
Starting Method:
Wye Start - Delta Run
Thermal Device - Bearing:
NONE (OLD)
Thermal Device - Winding:
None
Vibration Sensor Indicator
No Vibration Sensor
Winding Thermal 1:
None
Winding Thermal 2:
None
This post helps you to demystify the different types of motors so that you understand how they work and pick the right option. If you want more output from a motor, it is important to select the right one.
Read More| Brand | Pyramex |
| Model | RVZ2410SEX5 |
| Brand | Superlok |
| Model | SP-20M |
| Brand | SKF Bearing |
| Model | CMSS 2200 |
| Brand | Habasit America |
| Model | C0963S0750LFAA |
Item must be unused.
Item must be in it's original package.
Restocking, shipping and handling fees may apply to any return with this manufacturer.
For more information please consult https://www.mrosupply.com/page/returnwarranty-policy/