We never sell your data to third parties
ABB MO325-16 Manual Motor Starter Magnetic Only | 1SAM160000R1012
MODEL MO325-16
$298.13 Each
Prices are subject to change
FREE SHIPPING ON ORDERS OVER $100
Select Quantity
Typically Ships in: 1 day
Returnable:No
Actuator type
Rotary Handle
Ambient air temperature
Around the Enclosure 0 ... +40 C Operation -25 ... +50 C Storage -50 ... +80 C
Ambient air temperature compensation
No
Ampere rating UL/CSA
16 A
CB certificate
1SAA918000-2002
CCC certificate
1SAA918000-3806
Connecting capacity main circuit UL/CSA
Flexible 1/2x 14-8 AWG Stranded 1/2x 14-8 AWG
Contact position indication
ON / OFF
Conventional free-air thermal current (Ith)
Main Circuit 16 A
cUL certificate
cUL_E137861
cULus certificate
E137861
Data sheet, technical information
2CDC130002C0206
Declaration of conformity - CE
1SAD938506-0037
Degree of protection
IP20
DNV certificate
1SAA918000-0305
eClass
7.0 27370401
Electrical durability
50000 cycle
ETIM 4
EC000074 - Motor protective circuit-breaker
ETIM 5
EC000074 - Motor protective circuit-breaker
ETIM 6
EC000074 - Motor protection circuit-breaker
GL certificate
1SAA918000-0403
GOST certificate
1SAA918000-2703
LR certificate
1SAA918000-0503
Max operating altitude permissible
2000 m
Maximum operating voltage UL/CSA
Main Circuit 600 V AC
Mechanical durability
100000 cycle
Mounting position
Position 1 to 6
Number of poles
3
Object classification code
F
Pollution degree
3
Power loss
at Rated Operating Conditions per Pole 1.7 W
Rated frequency
Main Circuit 50 Hz Main Circuit 60 Hz
Rated impulse withstand voltage (U imp)
Main Circuit 6 kV
Rated instantaneous short-circuit current setting (Ii)
240 A
Rated insulation voltage (Ui)
690 V
Rated operational current (Ie)
16 A
Rated operational current AC-3 (Ie)
16 A
Rated operational voltage
Main Circuit 690 V AC Main Circuit 440 V DC
Rated service short-circuit breaking capacity (Ics)
(230 V AC) 100 kA (400 V AC) 60 kA (440 V AC) 40 kA (500 V AC) 25 kA (690 V AC) 4 kA
Rated ultimate short-circuit breaking capacity (Icu)
(230 V AC) 100 kA (400 V AC) 60 kA (440 V AC) 40 kA (500 V AC) 25 kA (690 V AC) 4 kA
Recommended screw driver
M3.5 Pozidriv 2
Resistance to shock acc. to IEC 60068-2-27
11 ms Pulse 15g
Resistance to vibrations acc. to IEC 60068-2-6
5g / 10 ... 150 Hz
RINA certificate
1SAA918000-0803
RMRS certificate
1SAA918000-0703
RoHS information
1SAA918001-4401
RoHS status
Following EU Directive 2002/95/EC August 18, 2005 and amendment
Standards
IEC/EN 60947-1 IEC/EN 60947-2 IEC/EN 60947-4-1 UL 508 CSA 22.2 No. 14
Tightening torque
Main Circuit 1.4 Nm
Tightening torque UL/CSA
Main Circuit 14 inlb
UL certificate
UL_E137861
Wire stripping length
Main Circuit 10 mm
Connecting capacity main circuit: Flexible with Ferrule 1/2x 0.75 ... 4 mm Flexible with Insulated Ferrule 1/2x 0.75 ... 4 mm Flexible 1/2x 1 ... 6 mm Rigid 1/2x 1 ... 6 mm
Horsepower rating UL/CSA: (220 ... 240 V AC) Three Phase 5 Hp (440 ... 480 V AC) Three Phase 10 Hp (550 ... 600 V AC) Three Phase 10 Hp
Mounting on DIN rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Remarks: For overload protection of the motors, an appropriate thermal or electronic overload relays must be used
Brand
Rexnord
Model
10177775
Brand
SKF Bearing
Model
7313 BECBM
Brand
Bando
Model
180J10
Brand
Dixon
Model
FOS12
Brand
TB Woods
Model
5J34
Brand
Stearns
Model
90201320K
Brand
Browning
Model
2739001
Brand
RAB Lighting
Model
LL22B