Call for Pricing - 888-671-2883
Typically Ships in: 1 day
Returnable: Yes
Degree of protection
Housing IP50Terminals IP20
Electrical durability
AC-12 100000 cycle
Measuring range
(L-L) 350 ... 580 V AC
Mechanical durability
30000000 cycle
Minimum switching capacity
24 V10 mA
Mounting position
1 ... 6
Output
2 x 1 c/o or 1 x 2 c/o contacts, configurable
Overvoltage category
III
Pollution degree
3
Rated control supply voltage
(L-L) 350 ... 580 V AC
Rated impulse withstand voltage
Input Circuit 8 kVOutput Circuit 4 kV
Rated insulation voltage
Input Circuit / Output Circuit 1000 VOutput Circuit 1 / Output Circuit 2 300 V
Rated operational current AC-12
(230 V) 4 A
Rated operational current AC-15
(230 V) 3 A
Rated operational current DC-12
(24 V) 4 A
Rated operational current DC-13
(24 V) 2 A
Recommended screw driver
4.50.8 x 4Pozidriv 1
Short-circuit protective devices
Output Circuit NC - F Type Fuses 6 AOutput Circuit NO - F Type Fuses 10 A
Tightening torque
0.6 ... 0.8 Nm
Time range
0 s or 0.1 ... 30 s tripping delay (ON or OFF)200 ms start-up delay
Wire stripping length
8 mm
The CM-MPN.52S is a multifunctional relay from the CM three-phase monitors range. It operates with a rated control supply voltage / three-phase measuring voltage of 350-580 V AC 50/60 Hz and has a 2 c/o (SPDT) output with contacts rated at 250 V / 4 A. This relay monitors all phase parameters such as over/undervoltage, phase unbalance and phase failure. The corresponding threshold values are adjustable. The CM-MPN.52S also offers selection of phase sequence monitoring, automatic phase sequence correction as well as an ON or OFF tripping delay. The output contacts can be configured as 1x2 c/o (SPDT) contacts (common signal) or 2x1 c/o (SPDT) contact (separate signal for over- and undervoltage thresholds) operation. The tripping delay is adjustable over a range of instantaneous to 30 s (0, 0.1-30 s). A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers screw connection technology with double-chamber cage connection terminals.